| 2005-02-23 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS NOW INCLUDE A |
| | GENERATOR WHICH HAS NOT BEEN PERMITTED. |
| | |
| | 2)NOTE: PLEASE SUBMIT FOR PERMIT, |
| | INCLUDE SITE PLAN SHOWING ALL SETBACKS |
| | FOR ZONING AND MEACHANICAL. |
| | PLEASE SUBMIT ALL MANUFACTURE SPECS FOR |
| | GENERATOR, ATS. |
| | PLEASE PROVIDE FUEL TYPE FOR PLUMB/MECH |
| | REVIEW. PLEASE PROVIDE CALCS FOR GAS. |
| | |
| | 3)NOTE: PLEASE SEE PLANS SUBMITTED, |
| | SHOWS A 150A MAIN FEEDING A 125A ATS AND |
| | 125A PANEL? |
| | |
| | 4)NOTE: PLEASE SEE RISER, PANEL SCHEDULE |
| | AND LOAD CALCS. |
| | NO DERATING MAY BE TAKEN FOR LOAD ON |
| | GENERATOR WITH AUTOMATIC TRANSFER. |
| | 700.5 |
| | |
| | 5)NOTE: PLEASE SHOW ALL ELECTRICAL ON |
| | PLANS. |
| | |
| | 6)NOTE: PLEASE SEE FBC FOR WIND LOADING |
| | ON GENERATOR. THIS INFORMATION WILL |
| | REQUIRED FOR MECH REVIEW. 140MPH |
| | |
| | 7)NOTE: PLEASE SEE 424.3B FOR OCP FOR |
| | AHU #1 7.5 KW ON A 30A BRKR. |
| | |
| | A HOLD WILL BE PLACED ONELEC PERMIT |
| | UNTIL GENERATOR HAS BEEN APPLIED FOR. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |