Plan Review Notes
Plan Review Notes For Permit 04050767
Permit Number 04050767
Review Stop E
Sequence Number 4
Notes
Date Text
2005-02-23 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS NOW INCLUDE A
 GENERATOR WHICH HAS NOT BEEN PERMITTED.
  
 2)NOTE: PLEASE SUBMIT FOR PERMIT,
 INCLUDE SITE PLAN SHOWING ALL SETBACKS
 FOR ZONING AND MEACHANICAL.
 PLEASE SUBMIT ALL MANUFACTURE SPECS FOR
 GENERATOR, ATS.
 PLEASE PROVIDE FUEL TYPE FOR PLUMB/MECH
 REVIEW. PLEASE PROVIDE CALCS FOR GAS.
  
 3)NOTE: PLEASE SEE PLANS SUBMITTED,
 SHOWS A 150A MAIN FEEDING A 125A ATS AND
 125A PANEL?
  
 4)NOTE: PLEASE SEE RISER, PANEL SCHEDULE
 AND LOAD CALCS.
 NO DERATING MAY BE TAKEN FOR LOAD ON
 GENERATOR WITH AUTOMATIC TRANSFER.
 700.5
  
 5)NOTE: PLEASE SHOW ALL ELECTRICAL ON
 PLANS.
  
 6)NOTE: PLEASE SEE FBC FOR WIND LOADING
 ON GENERATOR. THIS INFORMATION WILL
 REQUIRED FOR MECH REVIEW. 140MPH
  
 7)NOTE: PLEASE SEE 424.3B FOR OCP FOR
 AHU #1 7.5 KW ON A 30A BRKR.
  
 A HOLD WILL BE PLACED ONELEC PERMIT
 UNTIL GENERATOR HAS BEEN APPLIED FOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  