| Plan Review Notes For Permit 04050767 |
| Permit Number |
04050767 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-19 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GRND FROM PANEL "A" TO PANEL "B". | | | | | | 2 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT(S) IN | | | ONE BEDRM PER 210.52 | | | PLEASE SEE NO ROOM DESIGNATION SHOWN TO | | | VERIFY THIS. | | | | | | 4)NOTE: PLEASE SEE JACUZZI TUB SHOWN ON | | | PANEL SCHEDULE BUT NO INDICATION OF GFI | | | ON PLANS @ JACUZZI LOCATION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|