Plan Review Notes
Plan Review Notes For Permit 04050765
Permit Number 04050765
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) INDICATE OCCUPANCY/USAGE OF GARAGE
 BLDG. IF SERVICE GARAGE MORE COMMENTS
 SHALL BE FORTHCOMING.
 2) SHT A-2 A DRINKING FOUNTAIN IS REQUI-
 RED PER TABLE 403.1. - ALSO SEE SECTION
 410.1.
 3) SHT A-2 FLOOR PLAN, SHOW CLEAR FLOOR
 SPACE FOR THE TOILETS 11-4.16.2 AND THE
 LAVS 11-4.19.3.
 4) SJT A2 KITCHEN, SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. SUBMIT
 A DETAIL SHOWING COMPLIANCE.
 5) SHT A3 DETAILS # 1 & 2 H.C. ELEVAT-
 IONS, SHOW HEIGHT OF W/C'S 11-4.16.3 AND
 FOR LAVS EXPOSED PIPES AND SURFACES PER
 SECTION 11-4.19.4.
 6) SHT M-1 SHOW WATER HEATER LOCATION ON
 THE FLOOR PLAN. SUBMIT INFORMATION ON
 THE EMERGENCY PAN DRAIN LINE AND THE P/T
 RELIEF VALVE DISCHARGE LINE. WATER HEAT-
 ER SHALL BE ACCESSIBLE. SUBMIT A DETAIL.
 SECTIONS. 104.2.1 AND 501.4.
 7) SHT M-1 THERMAL EXPANSION CONTROL IS
 REQUIRED. SECTION 607.3.2
 8) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE LINE TO THE BLDG. SECTION
 608.13.2
 9) SHT M-1 WATER RISER DIAGRAM, PLEASE
 EXPLAIN WHICH FIXTURE IS BEING SUPPLIED
 WITH THE LINES PAST THE LAVS. - NO WATER
 SUPPLY IS SHOWN TO THE KITCHEN SINK.
 PLEASE CLARIFY. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]