| 2004-06-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) INDICATE OCCUPANCY/USAGE OF GARAGE |
| | BLDG. IF SERVICE GARAGE MORE COMMENTS |
| | SHALL BE FORTHCOMING. |
| | 2) SHT A-2 A DRINKING FOUNTAIN IS REQUI- |
| | RED PER TABLE 403.1. - ALSO SEE SECTION |
| | 410.1. |
| | 3) SHT A-2 FLOOR PLAN, SHOW CLEAR FLOOR |
| | SPACE FOR THE TOILETS 11-4.16.2 AND THE |
| | LAVS 11-4.19.3. |
| | 4) SJT A2 KITCHEN, SINK SHALL COMPLY |
| | WITH 11-4.24 AND ALL SUBSECTIONS. SUBMIT |
| | A DETAIL SHOWING COMPLIANCE. |
| | 5) SHT A3 DETAILS # 1 & 2 H.C. ELEVAT- |
| | IONS, SHOW HEIGHT OF W/C'S 11-4.16.3 AND |
| | FOR LAVS EXPOSED PIPES AND SURFACES PER |
| | SECTION 11-4.19.4. |
| | 6) SHT M-1 SHOW WATER HEATER LOCATION ON |
| | THE FLOOR PLAN. SUBMIT INFORMATION ON |
| | THE EMERGENCY PAN DRAIN LINE AND THE P/T |
| | RELIEF VALVE DISCHARGE LINE. WATER HEAT- |
| | ER SHALL BE ACCESSIBLE. SUBMIT A DETAIL. |
| | SECTIONS. 104.2.1 AND 501.4. |
| | 7) SHT M-1 THERMAL EXPANSION CONTROL IS |
| | REQUIRED. SECTION 607.3.2 |
| | 8) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE LINE TO THE BLDG. SECTION |
| | 608.13.2 |
| | 9) SHT M-1 WATER RISER DIAGRAM, PLEASE |
| | EXPLAIN WHICH FIXTURE IS BEING SUPPLIED |
| | WITH THE LINES PAST THE LAVS. - NO WATER |
| | SUPPLY IS SHOWN TO THE KITCHEN SINK. |
| | PLEASE CLARIFY. SECTION 104.2.1 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |