Plan Review Notes
Plan Review Notes For Permit 04050765
Permit Number 04050765
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.INDICATE OUTSIDE AIR DUCT, MATERIAL,
 SIZE, LAYOUT AND INTAKE.FRESH AIR
 INTAKE SHALL BE A MINIMUM OF 10 FT FROM
 STREETS, ALLEYS, PARKING LOT, LOADING
 DOCK, OR ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT OR FUMES.2001 FBC(M)
 401.5.1.
  
 3.INDICATE LOCATION FOR THE CONDENSING
 UNIT.ROOF INSTALLATIONS SHALL COMPLY
 WITH HEIGHT REQUIREMENTS OF THE 2001 FBC
 1511.7.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL FOR THE ROOF STAND.PLEASE
 NOTE, SHOULD ROOF HEIGHT EXCEED 16 FT,
 PERMANENT MEANS OF ACCESS IS REQUIRED
 PER 2001 FBC(M) 306.5.PLEASE CLARIFY.
  
 4.PLANS DO NOT INDICATE LINE SET FOR
 THE LIQUID & SUCTION LINES OR THE
 CONDENSATE.PLEASE INDICATE LINE SIZE,
 MATERIAL & LAYOUT.PROVIDE INFORMATION
 FOR THE TERMINATION OF THE CONDENSATE.
  
 5.PLEASE INDICATE IF ANY WORK IS TO
 BE DONE IN THE GARAGE AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.