Plan Review Notes
Plan Review Notes For Permit 04050765
Permit Number 04050765
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-19 00:00:001) ON PAGE E-1 IS APPEARS THAT ALL
 EMERGENCY LIGHTS AND EXIT SIGNS ARE
 LOCATED ON ONE SIDE OF THE BUILDING
 ONLY. THIS APPEARS TO BE INCORRECT AND
 MAKES THE BUILDING LOPSIDED. ALSO WITH
 THE EXIT SIGNS SHOWN HOW ARE YOU
 MEETING THE 1/3 WITH SPRINKLERS OR
 1/2 WITHOUT SPRINKLERS SEPARATION
 BETWEEN EXITS.
  
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF
 6" HIGH NUMBERS ARE REQUIRED.
  
 3) DEMOLITION, CONSTRUCTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 4) DEBRIS IS TO BE REMOVED FROM THE
 BUILDING DAILY.
  
 5) NO PORTABLE FIRE EXTINGUISHERS
 SHOWN.
  
 6) IS THE BUILDING SPRINKLER OR NON
 FIRE SPRINKLERED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910