| Plan Review Notes For Permit 04050765 |
| Permit Number |
04050765 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-19 00:00:00 | 1) ON PAGE E-1 IS APPEARS THAT ALL | | | EMERGENCY LIGHTS AND EXIT SIGNS ARE | | | LOCATED ON ONE SIDE OF THE BUILDING | | | ONLY. THIS APPEARS TO BE INCORRECT AND | | | MAKES THE BUILDING LOPSIDED. ALSO WITH | | | THE EXIT SIGNS SHOWN HOW ARE YOU | | | MEETING THE 1/3 WITH SPRINKLERS OR | | | 1/2 WITHOUT SPRINKLERS SEPARATION | | | BETWEEN EXITS. | | | | | | 2) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. A MINIMUM OF | | | 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 3) DEMOLITION, CONSTRUCTION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 4) DEBRIS IS TO BE REMOVED FROM THE | | | BUILDING DAILY. | | | | | | 5) NO PORTABLE FIRE EXTINGUISHERS | | | SHOWN. | | | | | | 6) IS THE BUILDING SPRINKLER OR NON | | | FIRE SPRINKLERED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|