| Plan Review Notes For Permit 04050765 |
| Permit Number |
04050765 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-21 00:00:00 | **************UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE(S). | | | PLEASE SEE SOME CIRCUITS ARE MISSING AND | | | SOME DO NOT MATCH W/ PANEL. | | | PLEASE SEE 700.12E FOR EM/EXT LTS | | | | | | 2)NOTE: SERVICE IS BEING SHOWN AS NEW? | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 3)NOTE: PLEASE INCLUDE COLD WATER PIPE | | | FOR GROUNDING ELECTRODE SYSTEM. 250.50 | | | | | | 4)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN | | | CIRCUITS.ALL. | | | | | | 5)NOTE: PLEASE SEE E-PLAN IS NOT SEALED, | | | BY ENGINEER.ONE SET SEEMS TO BE MISSING | | | SEAL. PLEASE SEAL SETS NEEDED. | | | FAC 61G15-23.002 IF ALL SETS ARE NEEDED | | | TO BE STAMPED, THEN ALL AREQ'D TO BE | | | SIGNED, DATED AND SEALED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|