Plan Review Notes
Plan Review Notes For Permit 04050765
Permit Number 04050765
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050765
 ADD: 1822 UPLAND RD
 CONT: BANES BUILDING CO
 TEL: (561)635-6935
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) UNITY OF TITLE, FOR
 74-43-43-29-004-0050
 74-43-43-29-004-0051
 REMOVAL OF BLOCK WALL AT PROPERTY LINE
 WILL REQUIRE THE UNITY OF TITLE.
  
 3) TO INCORPORATE THE NEW DOORS AND SIDE
 LIGHTS AT 2400 FLORIDA MANGO UNDER THIS
 PERMIT THE UNITITY OF TITLE WOULD ALSO
 NEED TO INCLUDE THIS LOT, OTHERWISE A
 SEPERATE PERMIT WOULD BE REQUIRED.
  
 4) 705.1.1.2 OPENINGS WITHIN 15'-0" OF
 THE PROPERTY LINE REQUIRE OPENING PROTEC
 TIVES, (45 MIN), THE NEW WEST DOORS,
 THE OPENINGS ON THE SOUTH, NEW AND EXIST
 ING.
  
 5) THE OCCUPANCY IS NOT CLEAR AS TO WHAT
 THIS BUILDING WILL BE USED FOR?
 IF THE USEAGE WILL BE AUTO REPAIR GARAGE
 SECTION411.5 (1-6) MUST BE TO BE IMPLE-
 MENTED. NOTE THAT (3) OTHER OCCUPANCIES
 ARE LOCATED IN OR ATTECHED ARE TO BE SEP
 ERATED AS 704. (2 HR). THIS APPLIES TO
 DOORS AND WINDOWS REQUIRING 1 1/2 HR
 PROTECTION. NOTE (4) VENTILATION REQIURE
 MENTS.PROVIDE THE 2HR RATING TO THE
 UNDER SIDE OF THE ROOF.
  
 6)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
  
 7)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8) NOTE RESTROOM DOOR BLOCKS EGRESS,
 1012.1.4 DURING ITS SWING ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED
 AT LEAST ONE HALF OF THE REQUIRED WIDTH
 OF AN CORRIDOR, PASSAGEWAY OR LANDING.
 THE CLEAR MINIMUM WIDTH REQUIRED IS 18".
  
 9) THE KITCHEN SINK HEIGHT NOT GIVEN,
 11-4.24.2 SINK SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34".
  
 10)11-4.16.4 MISSING THE GRAB BARS
 BEHIND THE WATER CLOSET. THE GRAB BAR BE
 HIND THE WATER CLOSET SHALL BE 36" MIN-
 IMUM. SEE FIGURE 29.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 12) SUBMIT THE CORRECT PRODUCT APPROVALS
 THE BEST ROLLING DOOR NOA DOESN'T MATCH
 THE STATE LISTING, SEE ATTACHED LISTING
 2ND PAGE LIST COVERED NOA'S.
  
 13) CERTIFIED TESTING REPORT SUBMITTED
 FOR SINGLE HUNG WINDOWS, PLANS DO NOT IN
 DICATE WHERE THEY ARE TO BE USED.
  
 14) MISSING NOA AND STATE LISTING FOR
 THE NEW 6068 STOREFRONT DOORS AND SIDE-
 LIGHTS.
  
 15) PLANS DO NOT INDICATE IF THE GLASS
 BLOCK ARE EXISTING OR NEW? IF NEW PRO-
 VIDE THE STATE LISTING AND NOA PLUS PRO-
 VIDE INFO. FOR THE 45 MIN FIRE RATING
 THAT IS REQUIRED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026