| 2004-05-19 00:00:00 | *************** UNSAT ************** |
| | |
| | 1)NOTE: PLEAS INDICATE GFI/GFI PROTECT- |
| | -ION JACUZZI TUB. 680 |
| | |
| | 2)NOTE: PLEASE SEE AN EQUIPMENT GROUND- |
| | -ING CONDUCTOR IS SHOWN FROM METER TO |
| | DISC "B". PLEASE SEE 250.6/250.24 |
| | |
| | 3)NOTE: PLEASE SEE 210.52C1 FOR MISSING |
| | RECEPTS ON KITCHEN COUNTERSPACE. |
| | |
| | 4)NOTE: PLEASE SEE 210.63 FOR MISSING |
| | GFI RECEPT FOR A/C COND UNITS. |
| | |
| | 5)NOTE: PLEASE SEE SEE RAISED SEAL MUST |
| | BE CLEAR AND VISABLE WITH ALL INFORMAT- |
| | -ION. PLEASE ALSO SEE FS 481.221, WHICH |
| | REQ'S A COMPLETE SIGNATURE. FIRST NAME |
| | IS SHOWN AS AN INITIAL. PLEASE ALSO |
| | SIGN FIRST NAME. PER DBPR. |
| | THIS IS REQ'D ON ALL PLANS WEATHER OR |
| | NOT COMMENT IS MADE BY OTHER REVIEWERS. |
| | |
| | 6 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 7)NOTE: PLEASE SEE ONE PANEL IS SHOWN |
| | IN GARAGE, PLEASE INDICATE LOCATION OF |
| | OTHER PANEL. |
| | |
| | 8)NOTE: PLEASE SEE SD IS REQ'D TO BE |
| | MOVED INTO MASTER BEDRM. NFPA-72 |
| | 8-1 |
| | |
| | |