| 2004-07-13 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GROUNDING ELECTRODE SYSTEM MUST | | | BE CONNECTED PER 250.24, NOT PAST THE | | | FIRST MEANS OF DISCONNECT. | | | | | | 2} THE RISER DIAGRAM REFERENCING | | | THE"FBC" IS INCORRECT, SHOULD BE "NEC". | | | THE INTENT IS TO INDICATE THE SIZE AND | | | TYPE (MATERIAL) OF THE GEC, NOT | | | REFERENCE THE ARTICLE REQUIRING IT. SEE | | | 104.2.1 FBC. | | | | | | 3} A RECEPTACLE IS REQUIRED WITHIN 25' | | | OF THE AIR CONDITIONING EQUIPMENT PER | | | 210.63 (NEC). PLEASE SHOW LOCATION OF | | | SAME ON DRAWING. | | | | | | 4} PLEASE DATE THE SEAL AT THE TIME OF | | | SIGNING THE PLANS PER 61G1-16.003 FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|