Plan Review Notes
Plan Review Notes For Permit 04050702
Permit Number 04050702
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE SYSTEM MUST
 BE CONNECTED PER 250.24, NOT PAST THE
 FIRST MEANS OF DISCONNECT.
  
 2} THE RISER DIAGRAM REFERENCING
 THE"FBC" IS INCORRECT, SHOULD BE "NEC".
 THE INTENT IS TO INDICATE THE SIZE AND
 TYPE (MATERIAL) OF THE GEC, NOT
 REFERENCE THE ARTICLE REQUIRING IT. SEE
 104.2.1 FBC.
  
 3} A RECEPTACLE IS REQUIRED WITHIN 25'
 OF THE AIR CONDITIONING EQUIPMENT PER
 210.63 (NEC). PLEASE SHOW LOCATION OF
 SAME ON DRAWING.
  
 4} PLEASE DATE THE SEAL AT THE TIME OF
 SIGNING THE PLANS PER 61G1-16.003 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026