Plan Review Notes
Plan Review Notes For Permit 04050702
Permit Number 04050702
Review Stop M
Sequence Number 1
Notes
Date Text
2004-05-27 00:00:00DENIED:
 PLEASE PROVIDE ENERGY & MANUAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13
 SUB-CHAPTER 600.
  
 PROVISO:
 RETURN AIR IS ALSO REQUIRED FROM THE
 MASTER BEDROOM AREA PER 2001 FBC(M)
 601.4.PLEASE REVISE PLANS INDICATING
 SIZE OF RETURN AIR DUCT & GRILLE.
 PLEASE NOTE, RETURN SHALL BE EQUAL TO
 THE TOTAL OF SUPPLY AIR TO THE MASTER
 SUITE.PLEASE PROVIDE REVISED PLAN
 PRIOR TO INSPECTION OR ON THE RE-SUB.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.