| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE INDICATE THE LOCATION OF |
| | ALL NEW EQUIPMENT, SERVICE AND A/C |
| | CONDENSERS. |
| | |
| | 2} SHOW GROUNDING IN COMPLIANCE WITH |
| | 250.50 (ALL THAT APPLY) AND 250.66 ON |
| | THE RISER. |
| | |
| | 3} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT.PER 110.9. |
| | |
| | 4} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3,210.8A1. |
| | |
| | 5} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | |
| | 5} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5} SHOW COMPLIANCE WITH 210.70(A)(2)(B). |
| | EGRESS LIGHTING. |
| | |
| | 6} PLEASE SEE PANEL SCHEDULE, SEVERAL |
| | CONDUCTORS HAVE INCORRECT OVERCURRENT |
| | PROTECTION PER 310.16(TABLE). CORRECT |
| | SAME. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |