Plan Review Notes
Plan Review Notes For Permit 04050702
Permit Number 04050702
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF
 ALL NEW EQUIPMENT, SERVICE AND A/C
 CONDENSERS.
  
 2} SHOW GROUNDING IN COMPLIANCE WITH
 250.50 (ALL THAT APPLY) AND 250.66 ON
 THE RISER.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.PER 110.9.
  
 4} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3,210.8A1.
  
 5} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
  
 5} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} SHOW COMPLIANCE WITH 210.70(A)(2)(B).
 EGRESS LIGHTING.
  
 6} PLEASE SEE PANEL SCHEDULE, SEVERAL
 CONDUCTORS HAVE INCORRECT OVERCURRENT
 PROTECTION PER 310.16(TABLE). CORRECT
 SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026