| Plan Review Notes For Permit 04050697 |
| Permit Number |
04050697 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04050697 | | | ADD: 600 NORTHPOINT PKWY | | | (PHASE V 2ND FL GUEST ROOMS | | | CORRIDOR & VENDING) WEST | | | CONT: AMERICAN BUILDING INTERIORS | | | TEL: (239)542-5717 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 2) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | | | | 3) SHOW THE MEANS OF EGRESS WITH IN | | | THE UNIT, DOUBLE/ DOUBLE SUITE, KING | | | SUITE. QUEEN/ QUEEN CONNECTOR HAS ONLY | | | 30" BETWEEN THE DRESSER AND THE CORNER | | | OF THE WALL. SEE TABLE 1004, 36" MINIMUM | | | CLEAR WIDTH. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|