Plan Review Notes
Plan Review Notes For Permit 04050697
Permit Number 04050697
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050697
 ADD: 600 NORTHPOINT PKWY
 (PHASE V 2ND FL GUEST ROOMS
 CORRIDOR & VENDING) WEST
 CONT: AMERICAN BUILDING INTERIORS
 TEL: (239)542-5717
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 3) SHOW THE MEANS OF EGRESS WITH IN
 THE UNIT, DOUBLE/ DOUBLE SUITE, KING
 SUITE. QUEEN/ QUEEN CONNECTOR HAS ONLY
 30" BETWEEN THE DRESSER AND THE CORNER
 OF THE WALL. SEE TABLE 1004, 36" MINIMUM
 CLEAR WIDTH.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026