| Date |
Text |
| 2004-06-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PER SECTION 11-9.2.3 (CHAPTER 509 FS) |
| | 1 UNIT REQUIRED TO COMPLY WITH ITEMS |
| | (1)(2)(3) - PROVIDE DETAILS AND ROOM |
| | NUMBER. |
| | 2) PER SECTION 11-9.1.3, 5 ROOMS IN ADD- |
| | ITION TO THOSE REQUIRED TO BE ACCESSIBLE |
| | SHALL BE PROVIDED WITH VISUAL ALARMS, |
| | NOTIFICATION DEFICES, AND TELEPHONE FOR |
| | PERSONS WITH HEARING IMPAIRMENTS. PLEASE |
| | PROVIDE INFORMATION, DETAILS, AND ROOM |
| | NUMBERS TO SHOW COMPLIANCE. |
| | 3) PER SECTION 11-9.1.4, SLEEPING ROOMS |
| | AND SUITES REQUIRED TO BE ACCESSIBLE BY |
| | 11-9.1.2 SHALL BE DISPERSED AMONG THE |
| | VARIOUS CLASSES OF SLEEPING ACCOMODAT- |
| | IONS AVAILABLE TO PATRONS OF THE PLACE |
| | OF TRANSIENT LODGING. PLANS INDICATE |
| | THAT NO ACCESSIBLE ROOMS OR SUITES ARE |
| | AVAILABLE FOR THE KING CONNECTOR, QUEEN/ |
| | QUEEN OR THE QUEEN/QUEEN CONNECTOR. |
| | PLEASE CLARIFY. |
| | 4) SHTS L101 & L305 DETAIL 11-10D - RE- |
| | MOVAL OF DRINKING FOUNTAIN, MINIMUM FAC- |
| | ILITIES REQUIRES A DRINKING FOUNTAIN PER |
| | TABLE 403.1. WILL THE DRINKING FOUNTAIN |
| | BE REPLACED/RELOCATED? IS THERE ANOTHER |
| | DRINKING FOUNTAIN AVAILABLE? PLEASE |
| | CLARIFY. |
| | 5) SHT L101 ITEM 11-17D - IN THE REMOVAL |
| | OF ANY PART OF A DRAINAGE SYSTEM, DEAD |
| | ENDS SHALL BE PROHIBITED. (OVER 2 FEET) |
| | SECTION 704.5. |
| | 6) MORE INFORMATION REQUIRED ON TITLE |
| | BLOCK FOR ARCHITECT. SEE FAC 61G1-16.004 |
| | AND FS 481.2055. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |