Plan Review Notes
Plan Review Notes For Permit 04050693
Permit Number 04050693
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PER SECTION 11-9.2.3 (CHAPTER 509 FS)
 1 UNIT REQUIRED TO COMPLY WITH ITEMS
 (1)(2)(3) - PROVIDE DETAILS AND ROOM
 NUMBER.
 2) PER SECTION 11-9.1.3, 5 ROOMS IN ADD-
 ITION TO THOSE REQUIRED TO BE ACCESSIBLE
 SHALL BE PROVIDED WITH VISUAL ALARMS,
 NOTIFICATION DEFICES, AND TELEPHONE FOR
 PERSONS WITH HEARING IMPAIRMENTS. PLEASE
 PROVIDE INFORMATION, DETAILS, AND ROOM
 NUMBERS TO SHOW COMPLIANCE.
 3) PER SECTION 11-9.1.4, SLEEPING ROOMS
 AND SUITES REQUIRED TO BE ACCESSIBLE BY
 11-9.1.2 SHALL BE DISPERSED AMONG THE
 VARIOUS CLASSES OF SLEEPING ACCOMODAT-
 IONS AVAILABLE TO PATRONS OF THE PLACE
 OF TRANSIENT LODGING. PLANS INDICATE
 THAT NO ACCESSIBLE ROOMS OR SUITES ARE
 AVAILABLE FOR THE KING CONNECTOR, QUEEN/
 QUEEN OR THE QUEEN/QUEEN CONNECTOR.
 PLEASE CLARIFY.
 4) SHTS L101 & L305 DETAIL 11-10D - RE-
 MOVAL OF DRINKING FOUNTAIN, MINIMUM FAC-
 ILITIES REQUIRES A DRINKING FOUNTAIN PER
 TABLE 403.1. WILL THE DRINKING FOUNTAIN
 BE REPLACED/RELOCATED? IS THERE ANOTHER
 DRINKING FOUNTAIN AVAILABLE? PLEASE
 CLARIFY.
 5) SHT L101 ITEM 11-17D - IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. (OVER 2 FEET)
 SECTION 704.5.
 6) MORE INFORMATION REQUIRED ON TITLE
 BLOCK FOR ARCHITECT. SEE FAC 61G1-16.004
 AND FS 481.2055.
  