2004-06-14 00:00:00*********** UNSAT *****************
  
 PLEASE SEE NOW AN ELECTRICAL PLAN/DRAW-
 -ING IS BEING SUBMITTED ALONG WITH A
 DESCIPTION OF WORK.
  
 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 TO INCLUDE NEW AND EXISTING. PLEASE SHOW
 LOAD CALC WITH NEW LOADS BEING ADDED.
 PLEASE SHOW SIZE OF EXSITNG PANEL/SERV-
 -ICE. PLEASE ALSO SHOW LOCATION OF PANEL
 215.5/220
  
 2)NOTE: PLEASE LIST BATH CIRCUITS PER
 210.11C3/ 20A #12.
  
 3)NOTE; PLEASE SEE NFPA-72 8-1
 SD'S ARE REQUIRED TO INSIDE AND OUTSIDE
 SLEEPING RMS AND REQUIRED TO BE WIRED
 INLINE.
 PLEASE ALSO SEE UNDER THE 2002 NEC THE
 SD'S IN BEDRMS MUST BE ARC FAULT PROTECT
 -ED. 210.12
  
 4)NOTE: PLANS NOW SHOW A NEW STEAM UNIT
 BEING ADDED. PLEASE SEE DUE TO COMBUST-
 -ABLES, STEAM UNIT MAY NOT BE LOCATED
 IN CLOTHES CLOSET.
 PLEASE PROVIDE SPECS FOR UNIT AND
 INFORMATION FOR CLEARENCE.
 PLEASE PROVIDE LOAD ON LOAD CALCS ALSO.
  
 5)NOTE: PLEASE SEE NEW LT BEING ADDED
 TO CLOSET/STORAGE? PLEASE SEE 410.8 FOR
 MIN FIXRURE TYPE AND MIN CLEARENCE
 REQ'D.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.