| 2004-06-14 00:00:00 | *********** UNSAT ***************** |
| | |
| | PLEASE SEE NOW AN ELECTRICAL PLAN/DRAW- |
| | -ING IS BEING SUBMITTED ALONG WITH A |
| | DESCIPTION OF WORK. |
| | |
| | 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE |
| | TO INCLUDE NEW AND EXISTING. PLEASE SHOW |
| | LOAD CALC WITH NEW LOADS BEING ADDED. |
| | PLEASE SHOW SIZE OF EXSITNG PANEL/SERV- |
| | -ICE. PLEASE ALSO SHOW LOCATION OF PANEL |
| | 215.5/220 |
| | |
| | 2)NOTE: PLEASE LIST BATH CIRCUITS PER |
| | 210.11C3/ 20A #12. |
| | |
| | 3)NOTE; PLEASE SEE NFPA-72 8-1 |
| | SD'S ARE REQUIRED TO INSIDE AND OUTSIDE |
| | SLEEPING RMS AND REQUIRED TO BE WIRED |
| | INLINE. |
| | PLEASE ALSO SEE UNDER THE 2002 NEC THE |
| | SD'S IN BEDRMS MUST BE ARC FAULT PROTECT |
| | -ED. 210.12 |
| | |
| | 4)NOTE: PLANS NOW SHOW A NEW STEAM UNIT |
| | BEING ADDED. PLEASE SEE DUE TO COMBUST- |
| | -ABLES, STEAM UNIT MAY NOT BE LOCATED |
| | IN CLOTHES CLOSET. |
| | PLEASE PROVIDE SPECS FOR UNIT AND |
| | INFORMATION FOR CLEARENCE. |
| | PLEASE PROVIDE LOAD ON LOAD CALCS ALSO. |
| | |
| | 5)NOTE: PLEASE SEE NEW LT BEING ADDED |
| | TO CLOSET/STORAGE? PLEASE SEE 410.8 FOR |
| | MIN FIXRURE TYPE AND MIN CLEARENCE |
| | REQ'D. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |