Plan Review Notes
Plan Review Notes For Permit 04050610
Permit Number 04050610
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-20 00:00:00*************DENIED*********************
 1) PLEASE PROVIDE CUT SHEET AND SPECS
 FOR ABOVEGROUND FUEL TANK.
  
 2) THE ABOVEGROUND FUEL TANK SHALL
 COMPLY WITH NFPA 30, 2000 EDITION.
  
 3) THE STORAGE ROOM FOR THE FUEL TANK
 MUST BE PROPERLY FIRE RATED.
  
 4) PER THE FIRE MARSHAL OF WEST PALM
 BEACH ABOVE GROUND TANKS ARE LIMITED TO
 500 GALS MAXIMUM. ( A LETTER IS REQUIRED
 FROM YOUR COMPANY REQUESTING,DUE TO THIS
 CONDO IS IN THE FIRE LIMIT)
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910