| Plan Review Notes For Permit 04050607 |
| Permit Number |
04050607 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-21 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | PLEASE NOTE THAT THE ARCHITECTS | | | SIGNATURE IS REQUIRED ON HIS/HER SEAL | | | PER 61G116.003.INITIALS ARE NOT | | | ACCEPTABLE. | | | | | | THE LOAD CALCULATIONS INDICATE TWO SMALL | | | APPLIANCE CIRCUITS, THE PANEL SCHEDULE | | | SHOWS THREE CIRCUITS,PLEASE CORRELATE. | | | | | | PLEASE NOTE THAT THE POOL SUBPANEL LOCAT | | | ION DOES NOT COMPLY WITH 110.26. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|