Plan Review Notes
Plan Review Notes For Permit 04050604
Permit Number 04050604
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-16 00:00:00DENIED
  
 1) THE NOTE ON SHEET 2 REFERS TO THE
 1997 STANDARD GAS CODE. PLEASE UPDATE
 TO THE 2001 FBC FUEL GAS CODE.
  
 2)A MEAN ROOF HEIGHT OF 25'-35' REQUIRES
 THE ROOF SHEATHING TO BE NAILED WITH 8D
 RING SHANK NAILS IN ZONE 3 PER CITY
 AMENDMENTS TO FBC TABLE 2306.1. REVISE
 ROOF SHEATHING NAILING NOTE ON SHEET 4.
  
 3) LIST THE ENGINEER'S FIRM LICENSE
 NUMBER IN THE TITLE BLOCK OF EVERY SHEET
 THAT IS SIGNED AND SEALED BY HIM AS
 REQUIRED BY FS 471.
  
 4) REVISE WOOD CONSTRUCTION NOTE 4 ON
 SHEET 6. THERE IS NO FBC 3218.17.
  
 5) SUBMIT THE UL LISTING INFORMATION FOR
 THE PREFAB FIREPLACE.
  
 6)THE TWO TRUSS ANCHOR UPLIFT SCHEDULES
 ON RF-1 AND SD-2 CONTAIN CONFLICTING
 INFORMATION. PLEASE REMOVE ONE OF THEM.
  
 7) THE USP TA16 CONNECTOR SPECIFIED ON
 SHEET RF-1, REQUIRES (9) 10D NAILS FOR
 AN UPLIFT OF 1205#. PLEASE CORRECT.
  
 8) THE ROYAL WALL ATTACHMENT PLAN IS FOR
 THE AUGUSTA GARAGE RIGHT AND THE SHOP
 DRAWINGS ARE FOR THE AUGUSTA GARAGE LEFT
 THE PANEL NUMBERS DO NOT CORRESPOND.
 THIS IS A SITE SPECIFIC ITEM. PLEASE
 SUBMIT THE APPROPRIATE INFORMATION.
  
 9) THE TRUSS LAYOUT PLAN DIFFERS QUITE A
 BIT FROM THE ROOF FRAMING PLAN ON RF-1.
 REVISE THE ROOF FRAMING PLAN TO MATCH
 THE LAYOUT PLAN FROM THE TRUSS COMPANY.
  
 10) THE TRUSS LAYOUT AND DRAWINGS DO NOT
 INCLUDE THE FLORIDA ROOM. PLEASE CORRECT
  
 11) THE TRUSS DRAWINGS ARE REQUIRED TO
 LIST A BOTTOM CORD LIVE LOAD OF AT LEAST
 10 PSF. SEE FBC TABLE 1604.1.
  
 12) SUBMIT DRAWINGS FOR THE F600 FIXED
 WINDOWS WITH THE CURRENT NOA 02-0701.08
 STAMPED ON THEM.
  
 13) WEATHERGUARD BUILDING PRODUCTS DOES
 NOT HAVE STATE PRODUCT APPROVAL FOR THE
 STORM PANELS. THE KEY PLAN AND SCHEDULE
 DO NOT SHOW THE IMPACT RATED EMERGENCY
 EGRESS WINDOW IN THE DEN. PLEASE CORRECT
 AND SUBMIT PRODUCT WITH STATE OR LOCAL
 PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714