| 2004-06-25 00:00:00 | BUILDING PROVISO: | | | PERMIT: 04050601 | | | ADDRESS: 622 N FLAGLER# 1204 | | | | | | 1)FOAM PLASTIC TRIM 803.4 | | | FOAM PLASTICS SHALL NOT BE USED AS INTER | | | IOR FINISHES. | | | EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS | | | PICTURE MOLDS, CHAIR RAIL, BASEBOARDS, | | | HANDRAILS CEILING BEAMS, DOOR TRIM AND | | | WINDOW TRIM, OR CROWN MOLDING SHALL BE | | | PERMITTED PROVIDED: | | | 1) THE MINIMUM DENSITY IS 20 LB/CU FT. | | | 2) THE MAXIMUM THICKNESS IS 1/2" AND | | | THE MAXIMUM WIDTH IS 4". | | | 3) THE TRIM CONSTITUTES NO MORE THAN | | | 10% OF THE AREA OF WALL OR CEILING. | | | 4) THE FLAMESPREAD RATING DOES NOT | | | EXCEED 75 WHEN TESTED PER ASTM E 84. THE | | | SMOKE DEVELOPMENT RATING IS NOT LIMITED. | | | | | | 2) SOFFITS: ARCHITECT TO SPECIFY THE | | | MINIMUM LENGTH OF FASTENRS TO STRUCTURE | | | ABOVE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|