2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) A WATER CLOSET SHALL BE SET NO CLOSER
 THAN 15" FROM ITS CENTER TO ANY SIDE
 WALL OR CLOSER THAN 30" CENTER TO CENTER
 TO ADJACENT FIXTURES. NEW ROOM FOR W/C
 AND LAV IS NOT WIDE ENOUGH. SECTION
 405.3.1
 2) A SANITARY RISER DIAGRAM AND A WATER
 RISER DIAGRAM ARE REQUIRED FOR NEW W/C
 AND LAV. SECTION 104.3.1.1.
  