| Notes |
| Date |
Text |
| 2004-05-18 00:00:00 | ********* UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE SPEC SHEET SUBMITTED | | | IS FOR A GAS HEATER?? | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR EXISTING ELECTRICAL SERVICE. | | | THIS IS TO INCLUDE ALL NEW AND EXSITING | | | LOADS. | | | PLEASE SEE ALL MOTOR LOADS ARE AT 100% | | | AND 125% FOR CONTINUOUS LOADS. (3OR MORE | | | HRS).HEAT PUMP INCLUDED. | | | LARGEST MOTOR AT 125%. | | | 215.3,230.42,220.19 ETC. | | | | | | 3)NOTE: PLEASE CORRELATE EQUIPMENT | | | SCHEDULE/PLUMB RISER AND WIRING DIAGRAM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|