Plan Review Notes
Plan Review Notes For Permit 04050579
Permit Number 04050579
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-18 00:00:00********* UNSAT ****************
  
 1)NOTE: PLEASE SEE SPEC SHEET SUBMITTED
 IS FOR A GAS HEATER??
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXISTING ELECTRICAL SERVICE.
 THIS IS TO INCLUDE ALL NEW AND EXSITING
 LOADS.
 PLEASE SEE ALL MOTOR LOADS ARE AT 100%
 AND 125% FOR CONTINUOUS LOADS. (3OR MORE
 HRS).HEAT PUMP INCLUDED.
 LARGEST MOTOR AT 125%.
 215.3,230.42,220.19 ETC.
  
 3)NOTE: PLEASE CORRELATE EQUIPMENT
 SCHEDULE/PLUMB RISER AND WIRING DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]