Plan Review Notes
Plan Review Notes For Permit 04050570
Permit Number 04050570
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A1.0 DEMO LEGEND #3 NOT FOUND.
 ALSO NOTHING INDICATING THAT THE EWC
 WILL BE REPLACED. PLEASE CLAIRFY. SECT-
 ION 104.2.1
 2) SHT A2.0 SHOW TURNING AREA FOR TOILET
 ROOM AND SHOWER IN AREA B. 104.2.1
 3) SHT A3.0 SHOW CLEAR FLOOR SPACE FOR
 ALL ACCESSIBLE FIXTURES. SEE SECTIONS
 11-4.15.5, 11-4.16.2, 11-4.18.3, 11-4.19
 .3 AND 11-4.22.3.
 - SHOW ACCESSIBLE W/C'S 18" OFF WALL TO
 CENTER OF FIXTURE PER FIGURE 30A AND 30E
 LAVS A MINIMUM OF 15" OFF WALL TO CENTER
 OF FIXTURE - LAV HIGHTS 34" TO FLOOD RIM
 LEVEL PER 11-4.19.2 - EXPOSED PIPES AND
 SURFACES PER 11-4.19.4 - SHOWER CONTROLS
 PER 11-4.21.5 - SHOWER UNIT PER SECTION
 11-4.21.6 - CURBS PER 11-4.21.7. PLEASE
 SHOW THESE REQUIREMENTS ON DETAILS.
 4) ENGINEER OF RECORD SHALL SIGN, SEAL,
 AND DATE ALL PLANS PROVIDED BY ENGINEER.
 FS 471.025.
  