Plan Review Notes
Plan Review Notes For Permit 04050569
Permit Number 04050569
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE FACILITIES PER TABLES 1003.1 (BLDG)
 AND 403.1 (PLMBG). INDICATE SQUARE FEET
 OF SPACE. SHOW ALL EXISTING TOILET ROOMS
 AND INDICATE NUMBER OF FIXTURES. SHOW
 LOCATION OF DRINKING FOUNTAINS ECT.
 2) ALL DEMO'D/CAPPED PIPING SHALL BE IN-
 SPECTED PRIOR TO COVERING.
 3) NO DEAD ENDS SHALL BE ALLOWED IN THE
 SANITARY SYSTEM PER SECTION 704.5.
 4) PLANS SHALL BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved