2004-06-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04050569
 ADD: 1041 45TH ST
 CONT: ANDERSON MOORE CONST CORP
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WHAT TYPE OF CONSTRUCTION, MINIMUM BUILD
 ING TYPE?
  
 3) SHEET A2.0 SECTION# 3, INDICATES THE
 REMOVAL OF A RAMP TO STAIRS:
 1003.2.7.2 WHERE THE CHANGE IN ELEVATION
 OF 12 IN. OR LESS OCCURS IN EXIT ACCESS
 CORRIDORS, EXITS AND EXIT DISCHARGE,
 RAMPS COMPLYING WITH 1013 SHALL BE PRO-
 VIDED.
 1003.2.7.1. WHERE A CHANGE IN LEVEL
 MEANS OF EGRESS NOT EXCEEDING 21 IN. IS
 ACHIEVED BY A STAIR, THE MINIMUM TREAD
 DEPTH OF SUCH STAIR SHALL BE 13 IN.
 AND THE PRESENCE AND LOCATION OF EACH
 STEP SHALL BE READILY APPARENT.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT DOOR & TRANSOM
 B) WINDOWS
 C) STORM SHUTTERS IF GLAZING ISN'T
 TESTED FOR LARGE MISSLE IMPACT
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) SHEET A1.1 ADMINISTRATION OFFICE,
 DOOR 102 DOESN'T MEET THE MINIMUM CLEAR-
 ENCE AT DOORS.11-4.13.6. INTERIOR SIDE
 REQUIRES 12".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026