| Plan Review Notes For Permit 04050494 |
| Permit Number |
04050494 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-14 00:00:00 | FAILED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERMIT APPLICATION INDICATES A | | | HEAT PUMP IS TO BE INSTALLED FOR THE | | | POOL.PLEASE PROVIDE THE FOLLOWING: | | | A) PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | B) THE SCHEMATIC MUST REFLECT THE HEAT | | | PUMP IN THE SYSTEM. | | | C) THE SCHEMATIC MUST SHOW THE TIME | | | CLOCK PLACED IN THE SYSTEM PER | | | 612.1.ABC.2.3.3 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|