| Plan Review Notes For Permit 04050410 |
| Permit Number |
04050410 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-14 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 04050410 | | | ADD: 1818 S AUSTRALIAN AV | | | CONT: RIENDEAU CONSTRUCTION | | | TEL: (561)722-5850 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)1004.1.4 WHERE 2 OR MORE EXITS OR | | | EXIT ACCESS DOORS ARE REQUIED, AT LEAST | | | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL | | | BE PLACED A DISTANCE APART EQUAL TO NOT | | | LESS THAN 1/2 OF THE LENGTH OF THE MAX- | | | IMUM OVERALL DIAGONAL DIMENSION OF THE | | | BUILDING OR AREA TO BE SERVED. | | | | | | 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 4) PROVIDE INFORMATION ON THE FIRE RAT- | | | ING OF THE ENTRY DOORS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|