Plan Review Notes
Plan Review Notes For Permit 04050402
Permit Number 04050402
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2 SANT. RISER DIAGRAM. A GATE
 VALVE LOCATED ON THE DISCHARGE SIDE OF
 THE CHECK VALVE SHAL BE INSTALLED IN THE
 EJECTOR DISCHARGE PIPING BETWEEN THE
 PUMP OR EJECTOR AND THE GRAVITY DRAINAGE
 SYSTEM. - ACCESS REQUIRED TO VALVES -
 SECTION 712.2. (SHOWN ON INLET SIDE OF
 THE PUMP/EJECTOR).
 2) PUMP SHALL BE LISTED - SUBMIT MANUF.
 SPECIFICATION SHEETS. SECTION 303.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]