| Notes |
| Date |
Text |
| 2005-01-25 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} WALL COUNTER SPACES. A RECEPTACLE | | | OUTLET SHALL BE INSTALLED AT EACH WALL | | | COUNTER SPACE THAT IS 300 MM (12 IN.) OR | | | WIDER. RECEPTACLE OUTLETS SHALL BE | | | INSTALLED SO THAT NO POINT ALONG THE | | | WALL LINE IS MORE THAN 600 MM (24 IN.) | | | MEASURED HORIZONTALLY FROM A RECEPTACLE | | | OUTLET IN THAT SPACE. | | | | | | 2} SMOKE DETECTORS PER 8-1.4.1.6 | | | NFPA-72. | | | | | | 3} OUTDOOR OUTLETS. FOR A ONE-FAMILY | | | DWELLING AND EACH UNIT OF A TWO-FAMILY | | | DWELLING THAT IS AT GRADE LEVEL, AT | | | LEAST ONE RECEPTACLE OUTLET ACCESSIBLE | | | AT GRADE LEVEL AND NOT MORE THAN 2.0 M | | | (61/2 FT) ABOVE GRADE SHALL BE INSTALLED | | | AT THE FRONT AND BACK OF THE DWELLING. | | | SEE 210.8(A)(3). | | | | | | NONE OF THESE REDLINED ITEMS WERE | | | CORRECTED ON THE REVISIONS.PLEASE | | | CORRECT SAME AND RESUBMIT FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|