2004-05-24 00:00:00PROVISO:
 1.RETURN AIR REQUIRED FROM HABITABLE
 ROOMS SEPARATED BY A DOOR.SEE THE
 ATTACHED SCHEDULE FOR PROPER SIZING OF
 THE RETURN AIR JUMPERS OR TRANSFER
 GRILLES.A DUCTED RETURN SHALL BE EQUAL
 TO THE SUPPLY AIR TO THAT SPACE PER 2001
 FBC(M) 601.4, REVISED JUNE 30, 2003
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  