Plan Review Notes
Plan Review Notes For Permit 04050289
Permit Number 04050289
Review Stop B
Sequence Number 1
Notes
Date Text
2004-07-13 00:00:00SENT TO DP DESK
2004-06-09 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE MAXIMUM HEIGHT ALLOWED FOR THE
 GARDEN WALL IS SIX FEET ABOVE FINAL
 GRADE. PLEASE CORRECT DETAIL ON SHEET 8.
  
 3) CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1 REQUIRES ROOF SHEATHING NAIL
 SPACING TO BE 4"OC AT EDGES AND 6"OC
 INTERMEDIATE. PLEASE REVISE NOTES ON
 SHEET 8.
  
 4) THE BUTT GLASS HEADER DETAIL ON 8 IS
 NOT APPLICABLE. PLEASE REMOVE OR CROSS
 OFF.
  
 5) WEATHERGUARD STORM PANELS DO NOT HAVE
 STATE PRODUCT APPROVAL. SUBMIT STORM
 PANELS WITH STATE OR LOCAL PRODUCT
 APPROVAL. THE KEY PLAN DOES NOT INDICATE
 THE IMPACT WINDOW FOR EGRESS IN THE DEN.
 INDICATE THE MOUNT TYPE AND FASTENERS
 BY HIGHLIGHTING OR CIRCLING THEM ON THE
 INSTALLATION DRAWINGS.
  
 6) TRUSS DRWINGS ARE NOT REQUIRED TO BE
 SUMITTED FOR PLAN REVIEW. THEY ARE
 REQUIRED TO BE GIVEN TO THE INSPECTOR IN
 THE FIELD AT THE TRUSS INSPECTION.
 - THE TRUSSES ARE REQUIRED TO HAVE A
 BOTTOM CORD LIVE LOAD OF 10PSF OR 30PSF.
 - THE CENTER BEARING POINT OF TRUSS FG-4
 HAS AN UPLIFT VALUE GREATER THAN THE ONE
 GIVEN ON THE PLAN. PLEASE CORRECT.
  