| 2004-07-13 00:00:00 | SENT TO DP DESK |
| 2004-06-09 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE MAXIMUM HEIGHT ALLOWED FOR THE |
| | GARDEN WALL IS SIX FEET ABOVE FINAL |
| | GRADE. PLEASE CORRECT DETAIL ON SHEET 8. |
| | |
| | 3) CITY OF WPB AMENDMENTS TO FBC TABLE |
| | 2306.1 REQUIRES ROOF SHEATHING NAIL |
| | SPACING TO BE 4"OC AT EDGES AND 6"OC |
| | INTERMEDIATE. PLEASE REVISE NOTES ON |
| | SHEET 8. |
| | |
| | 4) THE BUTT GLASS HEADER DETAIL ON 8 IS |
| | NOT APPLICABLE. PLEASE REMOVE OR CROSS |
| | OFF. |
| | |
| | 5) WEATHERGUARD STORM PANELS DO NOT HAVE |
| | STATE PRODUCT APPROVAL. SUBMIT STORM |
| | PANELS WITH STATE OR LOCAL PRODUCT |
| | APPROVAL. THE KEY PLAN DOES NOT INDICATE |
| | THE IMPACT WINDOW FOR EGRESS IN THE DEN. |
| | INDICATE THE MOUNT TYPE AND FASTENERS |
| | BY HIGHLIGHTING OR CIRCLING THEM ON THE |
| | INSTALLATION DRAWINGS. |
| | |
| | 6) TRUSS DRWINGS ARE NOT REQUIRED TO BE |
| | SUMITTED FOR PLAN REVIEW. THEY ARE |
| | REQUIRED TO BE GIVEN TO THE INSPECTOR IN |
| | THE FIELD AT THE TRUSS INSPECTION. |
| | - THE TRUSSES ARE REQUIRED TO HAVE A |
| | BOTTOM CORD LIVE LOAD OF 10PSF OR 30PSF. |
| | - THE CENTER BEARING POINT OF TRUSS FG-4 |
| | HAS AN UPLIFT VALUE GREATER THAN THE ONE |
| | GIVEN ON THE PLAN. PLEASE CORRECT. |
| | |