Plan Review Notes
Plan Review Notes For Permit 04050265
Permit Number 04050265
Review Stop P
Sequence Number 3
Notes
Date Text
2005-03-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEWS:
 1) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. THE SHR/TUB
 BETWEEN THE W/C AND THE LAVS IS NOT
 VENTED. SECTION 901.2.1.
 2) THE PERSONAL SIGNATURE SHALL APPEAR
 ON ALL ARCHITECTURAL DOCUMENTS TO BE
 FILED FOR PUBLIC RECORD. INITIALS ARE
 NOT ACCEPTABLE PER DBPR. SUBMIT
 DOCUMENTATION FOR YOUR LEGAL SIGNATURE
 ALONG WITH A SIGNED/SEALED/DATED AND
 NOTORIZED LETTER SHOWING LEGAL SIGNATURE
 WITH PROPER TITLE BLOCK INCLUDING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 OUR FILES. FAC 61G1-16.003
 3) A CERTIFICATE OF AUTHROIZATION SHALL
 BE REQUIRED FOR A CORPORATION,
 PARTNERSHIP, OR PERSON PRACTICING UNDER
 A FICTITIOUS NAME OFFERING ARCHITECTURAL
 SERVICES. FAC 61G1-16.004(2) & FS
 481.219.
 ***************NEW COMMENT************
 A) HAND DRAWN CHANGES TO A SIGNED &
 SEALED SET OF DRAWING IS NOT APPROVED.
 NEW SHEETS ARE REQUIRED FOR CHANGES
 REQUIRED BY COMMENTS. SECTION 104.2.1.3.
 B) SEE SHEET ATTACHED BY ELECTRICAL PLAN
 REVIEWER CONCERNING FS 553.80(2)(B) AND
 THE DESIGN PROFESSIONAL TO AVOID A 4
 TIMES THE FEE FOR PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  