| Date |
Text |
| 2005-03-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) FROM PREVIOUS REVIEWS: |
| | 1) SHT E-1 SANITARY RISER DIAGRAM DOES |
| | NOT MEET CODE REQUIREMENTS. THE SHR/TUB |
| | BETWEEN THE W/C AND THE LAVS IS NOT |
| | VENTED. SECTION 901.2.1. |
| | 2) THE PERSONAL SIGNATURE SHALL APPEAR |
| | ON ALL ARCHITECTURAL DOCUMENTS TO BE |
| | FILED FOR PUBLIC RECORD. INITIALS ARE |
| | NOT ACCEPTABLE PER DBPR. SUBMIT |
| | DOCUMENTATION FOR YOUR LEGAL SIGNATURE |
| | ALONG WITH A SIGNED/SEALED/DATED AND |
| | NOTORIZED LETTER SHOWING LEGAL SIGNATURE |
| | WITH PROPER TITLE BLOCK INCLUDING |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | OUR FILES. FAC 61G1-16.003 |
| | 3) A CERTIFICATE OF AUTHROIZATION SHALL |
| | BE REQUIRED FOR A CORPORATION, |
| | PARTNERSHIP, OR PERSON PRACTICING UNDER |
| | A FICTITIOUS NAME OFFERING ARCHITECTURAL |
| | SERVICES. FAC 61G1-16.004(2) & FS |
| | 481.219. |
| | ***************NEW COMMENT************ |
| | A) HAND DRAWN CHANGES TO A SIGNED & |
| | SEALED SET OF DRAWING IS NOT APPROVED. |
| | NEW SHEETS ARE REQUIRED FOR CHANGES |
| | REQUIRED BY COMMENTS. SECTION 104.2.1.3. |
| | B) SEE SHEET ATTACHED BY ELECTRICAL PLAN |
| | REVIEWER CONCERNING FS 553.80(2)(B) AND |
| | THE DESIGN PROFESSIONAL TO AVOID A 4 |
| | TIMES THE FEE FOR PLAN REVIEW. |
| | |
| | REVIEW BY KEN STEVENS |