| Plan Review Notes For Permit 04050265 |
| Permit Number |
04050265 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-02 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE RECALCULATE LOADS PER | | | 220.31(B), IF USING OPTIONAL | | | CALCULATIONS, 2002 NEC. SEE REVIEWED | | | SETTHE DRYER PER 220.18 AND A LAUNDRY | | | CIRCIUT PER 220.16(B). ALSO NOTE THE | | | A/C MUST BE AT 100%, THERE IS NO DEMAND. | | | | | | 2} A RECEPTACLE MUST BE ADDED TO THE | | | BEDROOM PER 210.52(A)(1). | | | | | | 3} THE NEW COMPRESSER MUST COMPLY WITH | | | 210.63, RECEPTACLE WITHIN 25'. | | | | | | 4} THE SEAL OF THE ARCHITECT MUST | | | CONTAIN THE DATE PREPARED PER | | | 61G1-16.003. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|