Plan Review Notes
Plan Review Notes For Permit 04050265
Permit Number 04050265
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE RECALCULATE LOADS PER
 220.31(B), IF USING OPTIONAL
 CALCULATIONS, 2002 NEC. SEE REVIEWED
 SETTHE DRYER PER 220.18 AND A LAUNDRY
 CIRCIUT PER 220.16(B). ALSO NOTE THE
 A/C MUST BE AT 100%, THERE IS NO DEMAND.
  
 2} A RECEPTACLE MUST BE ADDED TO THE
 BEDROOM PER 210.52(A)(1).
  
 3} THE NEW COMPRESSER MUST COMPLY WITH
 210.63, RECEPTACLE WITHIN 25'.
  
 4} THE SEAL OF THE ARCHITECT MUST
 CONTAIN THE DATE PREPARED PER
 61G1-16.003.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026