2004-05-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT E-1 SANITARY RISER DIAGRAM, THE
 TUB/SHOWER FIXTURES REQUIRE TRAPS PER
 SECTION 1002.1 - DWV PIPE NOT AVAILABLE
 IN 2-1/2" SIZE. 3" MINIMUM TO THE W/C'S
 AND 2" MINIMUM TO THE TUB/SHOWERS. MINI-
 MUM 1-1/2" TO LAV'S
 2) THE PERSONAL SIGNATURE AND DATE OF
 THE ARCHITECT SHALL APPEAR ON ALL ARCH-
 ITECTURAL DOCUMENTS TO BE FILED FOR PUB-
 LIC RECORD. INITIALS ARE NOT ACCEPTABLE
 PER DBPR. - A CERTIFICATE OF AUTHORIZAT=
 ION SHALL BE REQUIRED FOR A CORPORATION,
 PARTNERSHIP OR PERSON PRACTICING UNDER A
 FICTITIOUS NAME OFFERING ARCHITECTURAL
 SERVICES. FAC 61G1-16.003 & FS 481.219.
  