Plan Review Notes
Plan Review Notes For Permit 04050265
Permit Number 04050265
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED
 SERVICE SPECIFICATIONS PER 215.15.
  
 2} SMOKE DETECTORS ARE REQUIRED PER
 NFPA-72 8-1.4.1.6. INDICATE LOCATIONS
 ON PLAN.
  
 3} PROVIDE A PANEL SCHEDULE AS TO
 INDICATE CODE COMPLIANCE WITH THE
 FOLLOWING ATRICLES:
  
 A) PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11C3.
 B) PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 4} IF THE TITLE BLOCK ONTHE PLAN IS
 MEANT TO REPRESENT A FIRM AS OPPOSED TO
 THE ARCHITECT INDIVIDUALLY, IT MUST
 CONTAIN THE LICENSE NUMBER OF THE FIRM.
 SEE FAC 61G1-16.004.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved