| Plan Review Notes For Permit 04050265 |
| Permit Number |
04050265 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-12 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED | | | SERVICE SPECIFICATIONS PER 215.15. | | | | | | 2} SMOKE DETECTORS ARE REQUIRED PER | | | NFPA-72 8-1.4.1.6. INDICATE LOCATIONS | | | ON PLAN. | | | | | | 3} PROVIDE A PANEL SCHEDULE AS TO | | | INDICATE CODE COMPLIANCE WITH THE | | | FOLLOWING ATRICLES: | | | | | | A) PLEASE LIST ALL THE REQUIRED | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.11C3. | | | B) PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 4} IF THE TITLE BLOCK ONTHE PLAN IS | | | MEANT TO REPRESENT A FIRM AS OPPOSED TO | | | THE ARCHITECT INDIVIDUALLY, IT MUST | | | CONTAIN THE LICENSE NUMBER OF THE FIRM. | | | SEE FAC 61G1-16.004. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|