Plan Review Notes
Plan Review Notes For Permit 04050265
Permit Number 04050265
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-07 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 A. TIMBERLINE SHINGLES GAF
 B. PGT CASEMENT WINDOWS SERIES
 C-7IMPACTC. PGT SLIDING GLASS DOOR
 SERIES HS-70
 D. PGT HORIZONTAL SLIDING WINDOW HS-710
 E. PGT SERIES PW-701 IMPACT
 F. PGT SERIES SWD-101 FRENCH DOOR
 IMPACTG. CLOPLAY GARAGE DOOR TO 9' WIDE
 H. STRUCTURAL COMPONENTS (TRUSS STRAPES)
  
  
 2. THE PRODUCT APPROVAL FOR THE GARAGE
 DOOR HAS EXPIRED ON 8/21/03. (MIAMI/DADE
 GARAGE DOOR IS NOT SHOWN IN NEW ADDITION
  
 3. A-7 SECTION A-A SPECIFY #OF SIMPSON
 METAL STRAP TO BE USED ON TRUSS.
  
 4. A-7 SECTION B-B SPECIFY # OF SIMPSON
 METAL STRAP TO BE USED ON TRUSS.
  
 5. SHOW SCHEDUE OF EXISTING SQ. FOOTAGE
 AND NEW SQ. FOOTAGE A/C & NON A/C.
 UNDER ROOF TOTAL.
  
 6. ARDAMAN SOIL REPORT IS MISSING THE
 BORING LOGS.
  
 7. WINDOWS & DOORS ARE MISSING THE
 DESIGN PRESSURES ON A-5 & A-6
 ELEVATIONS.
  
 8. ELEVATION CERTIFICATE IS MISSING
 PAGE 2. SEE FORM ATTACHED.
  
 9. WINDOW & DOOR SCHEDULE MISSING.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713