| 2004-06-07 00:00:00 | BUILDING PLAN REVIEW FAILED: |
| | |
| | 1.PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONPLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | A. TIMBERLINE SHINGLES GAF |
| | B. PGT CASEMENT WINDOWS SERIES |
| | C-7IMPACTC. PGT SLIDING GLASS DOOR |
| | SERIES HS-70 |
| | D. PGT HORIZONTAL SLIDING WINDOW HS-710 |
| | E. PGT SERIES PW-701 IMPACT |
| | F. PGT SERIES SWD-101 FRENCH DOOR |
| | IMPACTG. CLOPLAY GARAGE DOOR TO 9' WIDE |
| | H. STRUCTURAL COMPONENTS (TRUSS STRAPES) |
| | |
| | |
| | 2. THE PRODUCT APPROVAL FOR THE GARAGE |
| | DOOR HAS EXPIRED ON 8/21/03. (MIAMI/DADE |
| | GARAGE DOOR IS NOT SHOWN IN NEW ADDITION |
| | |
| | 3. A-7 SECTION A-A SPECIFY #OF SIMPSON |
| | METAL STRAP TO BE USED ON TRUSS. |
| | |
| | 4. A-7 SECTION B-B SPECIFY # OF SIMPSON |
| | METAL STRAP TO BE USED ON TRUSS. |
| | |
| | 5. SHOW SCHEDUE OF EXISTING SQ. FOOTAGE |
| | AND NEW SQ. FOOTAGE A/C & NON A/C. |
| | UNDER ROOF TOTAL. |
| | |
| | 6. ARDAMAN SOIL REPORT IS MISSING THE |
| | BORING LOGS. |
| | |
| | 7. WINDOWS & DOORS ARE MISSING THE |
| | DESIGN PRESSURES ON A-5 & A-6 |
| | ELEVATIONS. |
| | |
| | 8. ELEVATION CERTIFICATE IS MISSING |
| | PAGE 2. SEE FORM ATTACHED. |
| | |
| | 9. WINDOW & DOOR SCHEDULE MISSING. |
| | |
| | ANY QUESTIONS PLEASE CALL: |
| | LEA SMITH, BUILDING PLANS EXAMINER |
| | 805-6713 |