Plan Review Notes
Plan Review Notes For Permit 04050240
Permit Number 04050240
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-11 00:00:00********** UNSAT********************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM AND
 PANEL SCHEDULE. BOTH SHOW PANELS AS
 MLO. MCB'S REQ'D. 225.31, ETC
  
 2)NOTE: PLEASE SEE MISSING SD INSIDE AND
 OUTSIDE GUEST BEDRM. PLEASE ALSO MOVE
 SD INTO MASTER BEDRM AREA. NFPA-71 8-1
  
 3)NOTE: PLEASE SEE MISSING RECEPT IN
 GUEST BATH PER 210.52D
  
 4)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C UNIT. 210.63
  
 5)NOTE: PLEASE SEE OUTLET SPACING FOR
 BEDRM #3. 210.52 RECEPT APPEARS TO BE
 IN CORNER BEHIND THE DOOR?
  
 6)NOTE: PLEASE SEE RECEPT SPACING ON
 KITCHEN COUNTERSPACE TO BE PER 210.52C1
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]