| Plan Review Notes For Permit 04050240 |
| Permit Number |
04050240 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-11 00:00:00 | ********** UNSAT******************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM AND | | | PANEL SCHEDULE. BOTH SHOW PANELS AS | | | MLO. MCB'S REQ'D. 225.31, ETC | | | | | | 2)NOTE: PLEASE SEE MISSING SD INSIDE AND | | | OUTSIDE GUEST BEDRM. PLEASE ALSO MOVE | | | SD INTO MASTER BEDRM AREA. NFPA-71 8-1 | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT IN | | | GUEST BATH PER 210.52D | | | | | | 4)NOTE: PLEASE SEE MISSING RECEPT FOR | | | A/C UNIT. 210.63 | | | | | | 5)NOTE: PLEASE SEE OUTLET SPACING FOR | | | BEDRM #3. 210.52 RECEPT APPEARS TO BE | | | IN CORNER BEHIND THE DOOR? | | | | | | 6)NOTE: PLEASE SEE RECEPT SPACING ON | | | KITCHEN COUNTERSPACE TO BE PER 210.52C1 | | | | | | 7 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|