| 2005-05-19 00:00:00 | ********** UNSAT ************ |
| | |
| | PLEASE SEE NOTES FROM PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #3 NO, PLEASE CORRELATE |
| | RISER WITH PANEL SCHEDULES SUBMITTED. |
| | PLEASE SEE PANEL SCHEDULE FOR M/M COMBO |
| | NOW SHOWS M/M AS 125A'SRISER SHOWS AS |
| | 400A'S. A 400A MCB WOULD BE REQUIRED. |
| | PLEASE SEE M/M COMBO SCHEDULE STILL DOES |
| | NOT INCLUDE THE 2-200A BRKRS FOR SUB |
| | PANELS AS SHOWN ON RISER. |
| | PLEASE SEE PANEL "B", THIS PANEL NOTES, |
| | FEED THRU LUGS TO "PANEL B"? PLEASE |
| | CLARIFY HOW THIS IS POSSIBLE IF RISER |
| | SHOWS (2) 200A BRKRS TO FEED EACH SUB |
| | PANEL? |
| | PLEASE SEE SEC'S ARE STILL BEING SHOWN |
| | AS 2/0'S. PLEASE SEE MIN SIZING PER |
| | 310.15B6 FOR A SF RESIDENCE. |
| | PLEASE SEE RISER ALSO INDICATES "FEED |
| | THRU" LUGS??? FOR ?? |
| | |
| | 2)NOTE: PLEASE SEE REVISED CALCULATIONS |
| | FOR EACH PANEL STILL NOT SUBMITTED. |
| | PLEASE ALSO SEE REVISED CALCULATIONS FOR |
| | SERVICE.? PLEASE SEE A/C LOAD NOTES 65%, |
| | HOWEVER 65% OF 20KW AAS SHOWN DOES NOT |
| | COME OUT TO 16250KW'S? IS THERE |
| | ADDITIONAL A/C LOAD? |
| | PLEASE SEE 220.31 |
| | |
| | PLEASE SEE OTHER NOTES WERE ADDRESSED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. ONCE AGAIN, IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CALL. |
| | |