Plan Review Notes
Plan Review Notes For Permit 04050206
Permit Number 04050206
Review Stop E
Sequence Number 4
Notes
Date Text
2005-05-19 00:00:00********** UNSAT ************
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #3 NO, PLEASE CORRELATE
 RISER WITH PANEL SCHEDULES SUBMITTED.
 PLEASE SEE PANEL SCHEDULE FOR M/M COMBO
 NOW SHOWS M/M AS 125A'SRISER SHOWS AS
 400A'S. A 400A MCB WOULD BE REQUIRED.
 PLEASE SEE M/M COMBO SCHEDULE STILL DOES
 NOT INCLUDE THE 2-200A BRKRS FOR SUB
 PANELS AS SHOWN ON RISER.
 PLEASE SEE PANEL "B", THIS PANEL NOTES,
 FEED THRU LUGS TO "PANEL B"? PLEASE
 CLARIFY HOW THIS IS POSSIBLE IF RISER
 SHOWS (2) 200A BRKRS TO FEED EACH SUB
 PANEL?
 PLEASE SEE SEC'S ARE STILL BEING SHOWN
 AS 2/0'S. PLEASE SEE MIN SIZING PER
 310.15B6 FOR A SF RESIDENCE.
 PLEASE SEE RISER ALSO INDICATES "FEED
 THRU" LUGS??? FOR ??
  
 2)NOTE: PLEASE SEE REVISED CALCULATIONS
 FOR EACH PANEL STILL NOT SUBMITTED.
 PLEASE ALSO SEE REVISED CALCULATIONS FOR
 SERVICE.? PLEASE SEE A/C LOAD NOTES 65%,
 HOWEVER 65% OF 20KW AAS SHOWN DOES NOT
 COME OUT TO 16250KW'S? IS THERE
 ADDITIONAL A/C LOAD?
 PLEASE SEE 220.31
  
 PLEASE SEE OTHER NOTES WERE ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]