| 2005-05-11 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR 10KW HEATSTRIPS. |
| | 125% MIN. |
| | |
| | 2)NOTE: PLEASE SEE PLANS MISSING RECEPT |
| | FOR WHIRLPOOL TUB. |
| | PLEASE ALSO SEE WP IS SHOWN AS 1-POLE |
| | 10A? BRKR W/2KW LOAD? |
| | 240.24,310.16 ETC. |
| | |
| | 3)NOTE: PLEASE CORRELATE PLANS , RISER |
| | DIAGRAM AND PANEL SCHEDULES. |
| | PLEASE SEE RISER SHOWS 200A DISC W/ 200A |
| | FUSES ON A 400A METER/MAIN COMBO? |
| | PLEASE SEE PLANS SHOW PANELS A AND B |
| | INSIDE GARAGE AND A METER AND A MAIN |
| | OUTSIDE? |
| | PLEASE SEE METER/MAIN COMBO SHOWS ONLY |
| | TWO BRKRS FOR A/C CU AND POOL EQUIPMENT. |
| | PLEASE SEE POOL EQUIPMENT IS ACTUALLY A |
| | POOL PANEL. PLEASE SHOW POOL PANEL ON |
| | PLANS, RISER AND SUBMIT PANEL SCHEDULE |
| | FOR POOL PANEL. |
| | |
| | *** PLEASE NOTE: METER/MAIN COMBO SHALL |
| | NOT HAVE MORE THAN 6 MIANS, OR 6 SPACES |
| | FOR MAINS. 230.70,230.71 ETC.*** |
| | |
| | 4)NOTE: PLEASE SEE NO REVISED LOAD |
| | CALCULATIONS WERE SUBMITTED EXCEPT FOR |
| | PANEL "C"? PLEASE CORRELATE LOAD |
| | CALCAULTIONS WITH PANEL SCHEDULES. |
| | 220.31, 215.5 |
| | |
| | PLEASE SEE TWO ITEMS REDLINED ON |
| | ORIGINAL PLANS NOT CORRECTED. |
| | |
| | 1)NOTE: PLEASE SEE LOGGIA AREA IN REAR |
| | OF HOUSE WILL REQUIRE A MIN OF ONE |
| | FIXTURE FOR MEANS OF EGRESS LIGHTING. |
| | 210.70, LS 101 5-8. |
| | |
| | 2)NOTE: PLEASE SEE MISSING RECEPT FOR 2' |
| | OF WALL SPACE IN STUDIO. 210.52 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |