2004-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT M-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) WASH MACHINE REQUIRES A STANDPIPE &
 A CLEANOUT. CLEANOUT SHALL BE INSTALLED
 4' ABOVE THE FLOOR FOR ACCESS. SECTIONS
 1002.1 & 708.10
 B) THE SIZE OF THE DRAINAGE PIPING
 SHALL NOT BE REDUCED IN SIZE IN THE DIR-
 ECTION OF FLOW. WASH MACHINE SHOWS 4"
 PIPE THEN REDUCING TO 2" PIPE. SECTION
 704.2.
 C) TUB AND SHOWER SHALL BE CONNECTED TO
 SANITARY BLDG DRAIN UNDERGROUND NOT UP
 ON THE STACK. SEE RED LINE CORRECTION.
 SECTION 102.4
 2) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE PER DPBR.
 FAC 61G1-16;003 & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]