2004-07-08 00:00:00****** NOTES REDLINED ***
  
 1)NOTE: NOTE #3 FROM FIRST REVIEW. THE
 CIRCUIT IS NOW SHOWN AS #14/15A.
 PLEASE SEE 210.52D,210.11C3, THIS
 DEDICATED BATH CIRCUIT MUST BE 20A AND
 #12.
  
 2)NOTE: PLEASE SEE 210.52C1 FOR RECEPT
 ALONG KITCHEN COUNTERSPACE.
  
 3)SD'S TO BE A MIN OF 3' FROM BATH DR.
 NFPA-72 8-1.4.2