| 2004-05-14 00:00:00 | DENIED: | | | 1.PLAN IS A COPY WITH AN ENGINEERS | | | SEAL & SIGNATURE.THIS IS PROHIBITED. | | | REFERENCE FA 471.025 & FAC 61G15-23.002. | | | SEE COMMENTS 1 & 2 BY DEWEY PALMER, | | | ELECTRICAL PLAN REVIEW. | | | | | | 2.RETURN AIR DUCTS ARE NOT SIZED ON | | | THE PLAN.SEE THE ATTACHED SCHEDULE FOR | | | PROPER SIZING OF RETURN AIR JUMPERS. | | | 2001 FBC(M) 601.4. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|