Plan Review Notes
Plan Review Notes For Permit 04050146
Permit Number 04050146
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-04 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) TITLE BLOCK IS MISSING INFORMATION.
 SEE FS 471.025 AND FAC 61G-23.002.
  
 4) SAFETY GLAZING IS REQUIRED IN BATH-
 ROOM WINDOWS THAT ARE WITHIN 3 FEET
 HORIZONTALLY OF THE TUB OR SHOWER. SEE
 2001 FBC 2405.2.
  
 5) CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1 REQUIRES NAILS TO BE 4"OC AT
 EDGES AND 6"OC INTERMEDIATE IN ZONE 3.
 PLEASE CORRECT NOTE ON SHEET 2.
  
 6) THE WALL SECTION ON SHEET 2 SPECS.
 SEMCO TRUSS CONNECTORS. PLEASE REVISE AS
 SEMCO IS NO LONGER IN BUSINESS.
  
 7) CLARIFY THE DIMENSIONS OF THE LUMBER
 FOR THE RAT RUNS ON THE WALL SECTION ON
 2.
  
 8) THE WALL SECTION ON 2 SPECIFIES A
 MIN. OF R4.2 WALL INSULATION AND THE
 ENERGY CALCS. SPECIFY R4.1. PLEASE
 CORRECT.
  
 9) SPECIFY THE CEILING MATERIAL FOR THE
 ENTRY CEILING (DIAPHRAGM).
  
 10) SPECIFY THE NUMBER/SPACING OF THE
 8"X 16" SOFFIT VENTS REQUIRED BY FBC
 2309.7.
  
 11) SPECIFY THE EXTERIOR FINISH FOR THE
 GABLE ENDS. SPECIFY THE ROOF OVERHANG AT
 THE GABLE ENDS.
  
 12) SPECIFY THE CLADDING MATERIAL FOR
 THE SOFFITS.
  
 13) SPECIFY THE UPLIFT PRESSURES OR THE
 TRUSS CONNECTORS ON THE TRUSS LAYOUT
 PLAN.
  
 14) SEVERAL DIMENSIONS ARE MISSING ON
 THE LEFT SIDE OF THE FOUNDATION PLAN.
  
 15) PROVIDE A KEY AND SCHEDULE FOR THE
 THE VERTICAL REINFORCEMENT OF THE WALLS
 AND COLUMNS ON THE FOUNDATION PLAN ON 3.
 INDICATE THE SIZE AND NUMBER OF THE
 REINFORCING BARS.
  
 16) CLARIFY THE DIMENSIONS ON THE SHOWER
 RECESS DETAIL.
  
 17) PROVIDE A KEY FOR THE FOOTINGS ON
 THE FOUNDATION PLAN AND TIE TO A FOOTER
 SCHEDULE.
  
 18) TERMITE PROTECTION IS REQUIRED PER
 FBC 1816.
  
 19) SPECIFY THE REQUIRED SOIL BEARING
 CAPACITY ON THE PLANS.
  
 20) THE DESIGN PRESSURES FOR THE WINDOW
 IN THE FAMILY ROOM THAT IS LOCATED IN
 THE EDGE STRIP ARE INCORRECT.
  
 21) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 22) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE MOUNT TYPE AND FASTENERS BY CIRCLING
 OR HIGHLIGHTING THEM ON THE INSTALLATION
 DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved