| 2004-05-14 00:00:00 | ******************PROVISO*************** | | | 2001 NFPA 96 7.8.2.1 (1) | | | EXHAUST TERMINATION SHALL BE A MINIMUM | | | OF 10 FT FROM PROPERTY LINES, ADJACENT | | | BUILDING OR FRESH AIR INTAKES. | | | | | | EHXAUST FAN SHALL COMPLY WITH NFPA 96 | | | 7.8.2.1 (8), HINGED, SERVICE HOLD OPEN | | | RETAINER, WITH A FLEXIBLE WEATHER-PROOF | | | ELECTRICAL CABLE. |
|