Plan Review Notes
Plan Review Notes For Permit 04050142
Permit Number 04050142
Review Stop M
Sequence Number 1
Notes
Date Text
2004-05-14 00:00:00******************PROVISO***************
 2001 NFPA 96 7.8.2.1 (1)
 EXHAUST TERMINATION SHALL BE A MINIMUM
 OF 10 FT FROM PROPERTY LINES, ADJACENT
 BUILDING OR FRESH AIR INTAKES.
  
 EHXAUST FAN SHALL COMPLY WITH NFPA 96
 7.8.2.1 (8), HINGED, SERVICE HOLD OPEN
 RETAINER, WITH A FLEXIBLE WEATHER-PROOF
 ELECTRICAL CABLE.