| Date |
Text |
| 2004-05-08 00:00:00 | ************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR NEW AND EXSITING LOADS FOR PANEL/ |
| | SERVICE. 220/215.5 |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRAM FOR |
| | SIZE OF CONDUCTORS SHOWN FOR NEW SUB |
| | PANEL. (MISPRINT) SHOWS 6/0'S AND 10/0'S |
| | FOR 60A PANEL. |
| | |
| | 3)NOTE: PLEASE SHOW GROUNDING SYSTEM AT |
| | DETACHED BLDG PER 250.32, NEW FOOTER, |
| | CWP (IF METALLIC). |
| | |
| | 4)NOTE: PLEASE INDICATE MEANS OF DISC |
| | AT DETACHED BLDG. IS THIS GOING TO BE |
| | A MCB IN NEW SUB PANEL. |
| | |
| | 5)NOTE: PLEASE SEE MISSING SD'S INSIDE |
| | STUDY/ ADAPTABLE SLEEPING RM PER NFPA-72 |
| | 8-1. |
| | PLEASE ALSO NOTE, THESE WILL BE REQ'D |
| | TO BE TIED INTO EXISTING/ NEW SD'S. |
| | |
| | 6)NOTE: PLEASE SEE FBC CHAPTER 34, |
| | 3401.7.2.6 VALUE EXCEEDING 50% OF EXSIT |
| | PLEASE PROVIDE LAYOUT OF EXISTING RES |
| | MEETING 2002 NEC. IF EXIST MEETS 2002 |
| | NEC, PLEASE SHOW AS. GFI/ARC FAULT, MIN |
| | CIRCUITS, SD'S ETC. |
| | |
| | 7)NOTE:P PLEASE SEE PLANS, NEXT TO NEW |
| | ADDITION, SHOWS NEW A/C UNIT, HOWEVER |
| | NEW CABANA ALSO SHOWS A/C UNITS, ARE |
| | THESE NEW OR EXSITING? |
| | PLEASE VERIFY IF NEW A/C FOR ADDITION |
| | IS FED FROM WHAT APPEARS TO BE NEW |
| | CABANA PANEL? |
| | |
| | PLEASE ALSO VERIFY OCP SHOWN FOR 5KW |
| | HEAT IN AHU. SHOWS 40A OCP. MIN. IS |
| | 125% PER 424.3B , PLEASE VERIFY MAX. |
| | |
| | 8) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 9)NOTE: PLEASE SEE NOTE UNDER RISER |
| | MENTIONS TO USE EXISTING CIRCUITS FOR |
| | NEW??? |
| | |
| | 10)NOTE: PLEASE SHOW LOCATION OF NEW |
| | PANEL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | 11)NOTE: PLEASE VERIFY IF NEW |