| 2004-10-07 00:00:00 | DENIED | | | | | | 1) THE VALUES LISTED IN THE TABLE IN | | | DETAIL 5 ON SHEET S2.03 FOR THE USP | | | THD28-2 CONNECTOR ARE INCORRECT. SEE | | | 2004 USP CATALOG. | | | | | | 2) THE STORM PANEL SCHEDULE INDICATES | | | STORM PANELS FOR THE FRONT DOOR. THIS | | | CONFLICTS WITH THE PLANS AND THE PRODUCT | | | APPROVAL WHICH SPECIFY AN IMPACT RATED | | | DOOR. PLEASE CLARIFY. | | | | | | 3) THE TRUSS LAYOUT AND DRAWINGS HAVE | | | NOT BEEN REVIEWED AND APPROVED BY THE | | | ARCHITECT. THEY ARE TO BE STAMPED AND | | | SIGNED BY HIM AS BEING REVIEWED AND | | | ACCEPTED. | | | | | | 4) THE ROOF FRAMING PLAN ON S2.03 IS NOT | | | CLEAR ON THE LOCATION AND UPLIFTS FOR | | | THE A3,A4 AND A5 TRUSSES WHICH HAVE | | | FOUR BEARING POINTS. PLEASE CORRECT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|