| Plan Review Notes For Permit 04050072 |
| Permit Number |
04050072 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-10 00:00:00 | ***UNSAT *** | | | | | | 1)NOTE: PLEASE SEE LOAD SHOWN FOR COND | | | UNIT AS 10KW, IF COOLING LOAD IS LARGER | | | THAN HEAT, THEN COOLING LAOD IS FIGURED | | | IN LAOD CALCS. PLEASE VERIFY, APPEARS | | | TO BE A MISPRINT FOR A 2.5 TON UNIT. | | | | | | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | SEE NEW RECEPT ADDED FOR PREVIOUS NOTES. | | | | | | 3)NOTE: PLEASE SEE 210.52C3 AND C5 FOR | | | PENINSULAR/WALL RECEPT SPACING. PLEASE | | | VERIFY IF RECEPT SHOWN IS FOR PENINSULAR | | | OR WALL. ? | | | PLEASE ALSO SEE 210.52 FOR 6' REQ'MENT. | | | | | | 4)NOTE: PLEASE SEE GEN NOTES#3 LAST | | | LINE MENTIONS RECEPTS TO BE ARC-FAULT | | | PROTECTED. | | | PLEASE SEE NEW NOTE ADDED. | | | | | | PLEASE SEE PLANS ARE ONLY IN FOR PLAN | | | REVIEW. THEY ARE ALSO FOR MASTERS WHICH | | | REQUIRES ALL TO BE 100% AND NO REDLINES | | | CAN BE DONE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|