Plan Review Notes
Plan Review Notes For Permit 04050072
Permit Number 04050072
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-10 00:00:00***UNSAT ***
  
 1)NOTE: PLEASE SEE LOAD SHOWN FOR COND
 UNIT AS 10KW, IF COOLING LOAD IS LARGER
 THAN HEAT, THEN COOLING LAOD IS FIGURED
 IN LAOD CALCS. PLEASE VERIFY, APPEARS
 TO BE A MISPRINT FOR A 2.5 TON UNIT.
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 SEE NEW RECEPT ADDED FOR PREVIOUS NOTES.
  
 3)NOTE: PLEASE SEE 210.52C3 AND C5 FOR
 PENINSULAR/WALL RECEPT SPACING. PLEASE
 VERIFY IF RECEPT SHOWN IS FOR PENINSULAR
 OR WALL. ?
 PLEASE ALSO SEE 210.52 FOR 6' REQ'MENT.
  
 4)NOTE: PLEASE SEE GEN NOTES#3 LAST
 LINE MENTIONS RECEPTS TO BE ARC-FAULT
 PROTECTED.
 PLEASE SEE NEW NOTE ADDED.
  
 PLEASE SEE PLANS ARE ONLY IN FOR PLAN
 REVIEW. THEY ARE ALSO FOR MASTERS WHICH
 REQUIRES ALL TO BE 100% AND NO REDLINES
 CAN BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW