| 2004-08-16 00:00:00 | DENIED |
| | |
| | 1) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE WORST CASE FOR MASTERED MODELS. |
| | THE A/C AREA ON THE PLANS AND ON THE |
| | ENERGY CALC. FORMS DO NOT MATCH. |
| | |
| | 2) DETAIL #5 ON S2.03 IS INCORRECTLY |
| | NUMBERED AS 201. THE THD28-2 DID NOT GET |
| | CHANGED TO THE THDH28-2, WHICH HAS THE |
| | UPLIFT OF 3185# THAT IS SPECIFIED. |
| | |
| | 3) SPECIFY ON SHEET S2.01 THAT THE |
| | FINISH FLOOR OF THE MONOLITHIC SLAB IS |
| | REQUIRED TO BE A MINIMUM OF 4" ABOVE |
| | FINAL GRADE AT HABITABLE AREAS. SEE CITY |
| | OF WPB AMENDMENTS TO FBC 1804.1.7. |
| | |
| | 4) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY |
| | THE INSTALLATION TYPE AND FASTENERS THAT |
| | WILL BE USED BY CIRCLING OR HIGHLIGHTING |
| | THE ITEMS ON THE INSTALLATION DRAWINGS. |
| | |
| | 5) THE PRODUCT APPROVAL FOR THE PGT SH |
| | 4000 WINDOWS DOES NOT MATCH THE NOA |
| | NUMBERS ON THE MIAMI-DADE NOA THAT WAS |
| | SUBMITTED. SUBMIT THE CORRECT NOA. ONLY |
| | ONE COPY WAS SUBMITTED. TWO COPIES ARE |
| | REQUIRED. |
| | |
| | 6) THE PRODUCT APPROVAL FOR THE PGT |
| | FRENCH DOOR DOES NOT MATCH THE NOA |
| | NUMBERS ON THE MIAMI-DADE NOA THAT WAS |
| | SUBMITTED. SUBMIT THE CORRECT NOA. |
| | |
| | 7) THE TRUSS LAYOUT IS TO BE REVIEWED BY |
| | THE ARCHITECT OF RECORD AND STAMPED AS |
| | APPROVED BY HIM. |
| | |
| | 8) THE TRUSS LAYOUT AND TRUSS DRAWINGS |
| | ARE REQUIRED TO HAVE THE ORIGINAL WET |
| | SIGNATURE OF THE TRUSS ENGINEER. SEE |
| | FAC 61G15-23.002. |
| | |
| | 9) TRUSSES A3, A4, AND A5 HAVE FOUR |
| | BEARING POINTS INDICATED ON THE TRUSS |
| | DRAWINGS. THE ROOF FRAMING PLANS ONLY |
| | SPECIFY CONNECTORS FOR THREE BEARING |
| | POINTS. PLEASE CORRECT. |
| | |
| | 10) THE TRUSS LAYOUT NOTES THAT THE |
| | BEAMS AT THE FRONT AND REAR PORCHES ARE |
| | BY BUILDER. SHEET S2.03 OF THE PLANS |
| | SPECIFY WOOD GIRDER TRUSSES. PLEASE |
| | CORRECT. IF BEAMS ARE BY BUILDER PROVIDE |
| | DETAILS. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |