| Notes |
| Date |
Text |
| 2004-05-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 2.01 SANITARY RISER DIAGRAM. THE | | | TRAPS FOR THE TUB ARE "S" TRAPS AS SHOWN | | | AND ARE NOT ALLOWED PER SECTION 1002.3 | | | - ANY PORTION OF THE DRAINAGE SYSTEM IN- | | | STALLED UNDERGROUND SHALL NOT BE LESS | | | THAN 2". SECTION 710.3 - WASH MACHINE | | | DRAIN REQUIRES A TRAP, A STANDPIPE, AND | | | A CLEANOUT. THE CLEANOUT SHALL BE MIN. | | | 4' ABOVE THE FLOOR FOR ACCESS. SEE SECT- | | | IONS 1002.1, 802.4, & 708.10. | | | 2) 2" SHOWN TO WATER CLOSETS. SUBMIT | | | MANUF. SPECIFICATION SHEETS INDICATING | | | FIXTURE OUTLET SIZE. SEE FOOTNOTE D FOR | | | TABLE 709.1 | | | 3) SEE RED LINE CORRECTIONS ON SHEET | | | P2.01. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|