2004-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2.01 SANITARY RISER DIAGRAM. THE
 TRAPS FOR THE TUB ARE "S" TRAPS AS SHOWN
 AND ARE NOT ALLOWED PER SECTION 1002.3
 - ANY PORTION OF THE DRAINAGE SYSTEM IN-
 STALLED UNDERGROUND SHALL NOT BE LESS
 THAN 2". SECTION 710.3 - WASH MACHINE
 DRAIN REQUIRES A TRAP, A STANDPIPE, AND
 A CLEANOUT. THE CLEANOUT SHALL BE MIN.
 4' ABOVE THE FLOOR FOR ACCESS. SEE SECT-
 IONS 1002.1, 802.4, & 708.10.
 2) 2" SHOWN TO WATER CLOSETS. SUBMIT
 MANUF. SPECIFICATION SHEETS INDICATING
 FIXTURE OUTLET SIZE. SEE FOOTNOTE D FOR
 TABLE 709.1
 3) SEE RED LINE CORRECTIONS ON SHEET
 P2.01.
  
 REVIEW BY KEN STEVENS