| Plan Review Notes For Permit 04050072 |
| Permit Number |
04050072 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-14 00:00:00 | DENIED: | | | 1.RETURN AIR TO THE MASTER BEDROOM IS | | | NOT SIZED PROPERLY.ALL SUPPLY AIR TO | | | THE MASTER SUITE IS TO BE INCLUDED FOR | | | THE "TOTAL" OF SUPPLY AIR.SUPPLY AIR | | | 7" TO THE BEDROOM 6" TO THE BEDROOM FOR | | | A TOTAL OF 66 SQ INCHES MULTIPY BY 1.5 | | | EQUALS A TOTAL OF 99 SQ INCHES THEREFOR | | | RETURN AIR SHOULD BE A MINIMUM OF 12". | | | | | | 2.SUPPLY AIR DUCT TO BEDROOM #2 IS | | | NOT SIZED. | | | | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 402.2 OR 403.3 OF THE 2001 FBC(M). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|