2004-05-14 00:00:00DENIED:
 1.RETURN AIR TO THE MASTER BEDROOM IS
 NOT SIZED PROPERLY.ALL SUPPLY AIR TO
 THE MASTER SUITE IS TO BE INCLUDED FOR
 THE "TOTAL" OF SUPPLY AIR.SUPPLY AIR
 7" TO THE BEDROOM 6" TO THE BEDROOM FOR
 A TOTAL OF 66 SQ INCHES MULTIPY BY 1.5
 EQUALS A TOTAL OF 99 SQ INCHES THEREFOR
 RETURN AIR SHOULD BE A MINIMUM OF 12".
  
 2.SUPPLY AIR DUCT TO BEDROOM #2 IS
 NOT SIZED.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 402.2 OR 403.3 OF THE 2001 FBC(M).
  