Plan Review Notes
Plan Review Notes For Permit 04050072
Permit Number 04050072
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-10 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 PANEL AS MCB AND YET PLANS/RISER SHOWS
 A MAIN DISCONNECT?
 A MCB IS PERMITTED BUT NOT REQ'D. IF
 SHOWN ON PLANS THEN IT MUST BE INSTALLED
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110, SIZE PER 250.122.
  
 3)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. 2', 6',12'
  
 4)NOTE: PLEASE SEE OCP/AWG SHOWN FOR
 2.5TON A/C COND UNIT. THIS SEEMS TO BE
 TOO HIGH FOR OCP.
  
 5)NOTE: PLEASE SHOW MAIN DISC NEXT TO
 METER ON PLANS.
  
 6)NOTE: DISC FOR A/CTO MEET 110.26,
 SHOWN BEHIND UNIT.
  
 7)NOTE: PLEASE IDENTIFY ARC FAULT PER
 2002 NEC. 210.12B WHICH REQ'S ALL OUTLET
 S. SD'S, RECEPTS, LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  