2004-06-02 00:00:00DENIED
  
 1) SUBMIT TRUSS DRAWINGS AND LAYOUT THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.
  
 2) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE WORST CASE FOR MODELS. THE FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT. THE CONDITIONED FLOOR AREA
 ON THE FORM AND THE PLANS SHOULD BE THE
 SAME.
  
 3) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE 2001 FBC TABLE 1604.1.
  
 4) THE MONOLITHIC FOOTING IN THE WALL
 SECTION ON S 2.01 DOES NOT CORRESPOND
 WITH THE F1 FOOTING IN THE SCHEDULE.
 PLEASE CORRECT.
  
 5) THE ISOLATED PAD DETAIL ON S 2.01 IS
 INCORRECTLY LABELED AS 7. IT SHOULD BE
 LABELED 4.
  
 6) SPECIFY THE MATERIAL USED FOR THE
 CEILINGS (DIAPHRAGM) OF THE COVERED
 PORCHES.
  
 7) SUBMIT STATE PRODUCT APPROVALS FOR
 THE USP CONNECTORS.(HLPTA75, TA16, RT16F
 RT22T, THD28-2)
  
 8) THE USP THD28-2 HAS A MAXIMUM UPLIFT
 OF 2390# AT 133% PER 2004 USP CATALOG.
 PLEASE REVISE DETAIL 5 ON S 2.03.
 (THE THDH28-2 HAS AN UPLIFT OF 3185#.)
  
 9) THE EXTERIOR WALLS AT THE REAR PORCH
 ARE NOT SHOWN ON THE ROOF FRAMING PLAN
 ON S2.03.
  
 10) ON S3.01 THE WALL SHEATHING IS
 SPECIFIED AS 15/32" IN ONE PLACE AND
 5/8" IN ANOTHER. PLEASE CORRECT.
  
 11) THE ROOF SHEATHING IS INCORRECTLY
 SPECIFIED AS 15/32" ON SHEET S3.01. CITY
 OF WPB AMENDMENTS TO FBC TABLE 2309.3A
 REQUIRES MINIMUM 19/32" SHEATHING.
  
 12) CITY AMENDMENTS TO FBC TABLE 2306.1
 REQUIRES ROOF SHEATHING TO BE NAILED AT
 4"OC ON THE EDGES AND 6"OC INTERMEDIATE
 IN ZONE 3 WHICH INCLUDE THE CORNERS OF
 HIP ROOFS. PLEASE REVISE NOTES ON S3.01.
  
 13) PLEASE UPDATE THE ACI EDITIONS THAT
 ARE SPECIFIED ON S3.01 TO 2002 EDITIONS
 PER FBC CHAPTER 35. SEE NOTES ON THE
 PLAN.
  
 14) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE INSTALLATION TYPE AND FASTENERS THAT
 WILL BE USED BY CIRCLING OR HIGHLIGHTING
 APPROPRIATE ITEMS ON THE INSTALLATION
 DRAWINGS.
  
 15) SUBMIT STATE PRODUCT APPROVALS FOR
 THE FOLLOWING ITEMS:
 - SINGLE OUTSWING DOOR AT THE KITCHEN
 - DOUBLE OUTSWING DOORS AT STORAGE
 - ALUMINUM SOFFIT
 - TRUSS CONNECTORS
  
 16) ONE OF THE PRODUCT APPROVALS FOR THE
 STORM PANELS IS MISSING THE INSTALLATION
 DRAWINGS.
  
 THE FOLLOWING ITEMS WILL BE REQUIRED TO
 BE SUBMITTED FOR EACH PERMIT APPLICATION
 UNDER THE MASTER.
 - NOTICE OF COMMENCEMENT
 - PAID RECEIPT FOR COUNTY IMPACT FEES.
 (PLANS MUST BE STAMPED BY COUNTY)
 - A SURVEY
 - A SUBSURFACE SOIL REPORT(FBC 1804.2.2)
  