| 2004-06-02 00:00:00 | DENIED |
| | |
| | 1) SUBMIT TRUSS DRAWINGS AND LAYOUT THAT |
| | HAVE BEEN REVIEWED AND APPROVED BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 2) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE WORST CASE FOR MODELS. THE FORM IS |
| | REQUIRED TO BE SIGNED AND DATED BY THE |
| | OWNER/AGENT. THE CONDITIONED FLOOR AREA |
| | ON THE FORM AND THE PLANS SHOULD BE THE |
| | SAME. |
| | |
| | 3) SPECIFY THE BOTTOM CORD LIVE LOAD ON |
| | THE PLANS. SEE 2001 FBC TABLE 1604.1. |
| | |
| | 4) THE MONOLITHIC FOOTING IN THE WALL |
| | SECTION ON S 2.01 DOES NOT CORRESPOND |
| | WITH THE F1 FOOTING IN THE SCHEDULE. |
| | PLEASE CORRECT. |
| | |
| | 5) THE ISOLATED PAD DETAIL ON S 2.01 IS |
| | INCORRECTLY LABELED AS 7. IT SHOULD BE |
| | LABELED 4. |
| | |
| | 6) SPECIFY THE MATERIAL USED FOR THE |
| | CEILINGS (DIAPHRAGM) OF THE COVERED |
| | PORCHES. |
| | |
| | 7) SUBMIT STATE PRODUCT APPROVALS FOR |
| | THE USP CONNECTORS.(HLPTA75, TA16, RT16F |
| | RT22T, THD28-2) |
| | |
| | 8) THE USP THD28-2 HAS A MAXIMUM UPLIFT |
| | OF 2390# AT 133% PER 2004 USP CATALOG. |
| | PLEASE REVISE DETAIL 5 ON S 2.03. |
| | (THE THDH28-2 HAS AN UPLIFT OF 3185#.) |
| | |
| | 9) THE EXTERIOR WALLS AT THE REAR PORCH |
| | ARE NOT SHOWN ON THE ROOF FRAMING PLAN |
| | ON S2.03. |
| | |
| | 10) ON S3.01 THE WALL SHEATHING IS |
| | SPECIFIED AS 15/32" IN ONE PLACE AND |
| | 5/8" IN ANOTHER. PLEASE CORRECT. |
| | |
| | 11) THE ROOF SHEATHING IS INCORRECTLY |
| | SPECIFIED AS 15/32" ON SHEET S3.01. CITY |
| | OF WPB AMENDMENTS TO FBC TABLE 2309.3A |
| | REQUIRES MINIMUM 19/32" SHEATHING. |
| | |
| | 12) CITY AMENDMENTS TO FBC TABLE 2306.1 |
| | REQUIRES ROOF SHEATHING TO BE NAILED AT |
| | 4"OC ON THE EDGES AND 6"OC INTERMEDIATE |
| | IN ZONE 3 WHICH INCLUDE THE CORNERS OF |
| | HIP ROOFS. PLEASE REVISE NOTES ON S3.01. |
| | |
| | 13) PLEASE UPDATE THE ACI EDITIONS THAT |
| | ARE SPECIFIED ON S3.01 TO 2002 EDITIONS |
| | PER FBC CHAPTER 35. SEE NOTES ON THE |
| | PLAN. |
| | |
| | 14) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY |
| | THE INSTALLATION TYPE AND FASTENERS THAT |
| | WILL BE USED BY CIRCLING OR HIGHLIGHTING |
| | APPROPRIATE ITEMS ON THE INSTALLATION |
| | DRAWINGS. |
| | |
| | 15) SUBMIT STATE PRODUCT APPROVALS FOR |
| | THE FOLLOWING ITEMS: |
| | - SINGLE OUTSWING DOOR AT THE KITCHEN |
| | - DOUBLE OUTSWING DOORS AT STORAGE |
| | - ALUMINUM SOFFIT |
| | - TRUSS CONNECTORS |
| | |
| | 16) ONE OF THE PRODUCT APPROVALS FOR THE |
| | STORM PANELS IS MISSING THE INSTALLATION |
| | DRAWINGS. |
| | |
| | THE FOLLOWING ITEMS WILL BE REQUIRED TO |
| | BE SUBMITTED FOR EACH PERMIT APPLICATION |
| | UNDER THE MASTER. |
| | - NOTICE OF COMMENCEMENT |
| | - PAID RECEIPT FOR COUNTY IMPACT FEES. |
| | (PLANS MUST BE STAMPED BY COUNTY) |
| | - A SURVEY |
| | - A SUBSURFACE SOIL REPORT(FBC 1804.2.2) |
| | |
| | IF YOU HAVE QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |